Item # Model 560D/P, Model 561D or P, Sulfur Dioxide Alarm Monitor, diffusion or pump, Wall Mounted



The Nova 560 Series Sulfur Dioxide (SO2) alarm monitors are designed for the continuous detection of SO2 in ambient air. The SO2 sensor is capable of excursions over 100 PPM with no damage. The SO2 sensor is of the disposable electrochemical type with an expected life of between 2-3 years. The sensor needs no warm up time and is ready to go as soon as the monitor is turned on. Two versions are available as shown below.

Models:

  • 560D - Diffusion sensor, no pump and no moving parts; excellent for monitoring in immediate local environment
  • 560P - Pumped sample version; pump pulls air sample from wider area or from another isolated environment, such as from a closed room





Specifications  · Applications  · Features  · Options  · Calibration  · Unique Applications

Specifications

Method of Detection

Customer replaceable electrochemical SO2 sensor

Ranges Available

0-20 PPM standard

Resolution

1 PPM

Accuracy & Repeatability

Better than ±1% of full scale

Drift

Less than 1% of full scale per week

Response Time (T-90)

Less than 60 seconds to 90% step change

Ambient Temperature Range

40 to 104°F (4 to 40°C)

Linearity

±1% of full scale

Size & Weight

20" H x 16" W x 10" D @ 20lbs. (51 x 41 x 26 cm @ 10kg)

Power

115 VAC, 60 Hz
220 VAC, 50 Hz

Output Options

4-20 mA

Analyzer Type

Wall-mounted Ambient Air Monitor

Area Rating

General Purpose Non-Hazardous only


Applications
Designed to monitor ambient sulfur dioxide (SO2) near industrial processes, in confined spaces, or any other area where SO2 may be present.



Features
  • Fast response to the presence of SO2
  • Instant warm up, no wait
  • Bright digital readout
  • Easy to use and calibrate
  • Modular layout that is easy to maintain
  • 4-20mA output signal for recording
  • NEMA 12 dust-tight enclosure




Options
  • Low flow alarm on pumped sample models
  • NEMA 4 weather-proof enclosures
  • Alarm with relay contact and 'Sonalert' audible alarm with 'Acknowledge' button
  • Bright red strobe light for visible alarming




Calibration
  • On N2 for zero
  • Analyzed calibration gas of SO2 in N2 for span




Unique Applications
All Nova analyzers are built using proven technologies and techniques. However, the 560 Series is not suitable for many process or flue gas applications. If this product does not suit your application, please contact Nova at 1-800-295-3771. In many cases, we are able to build an analyzer specific to your needs.



 MORE IMAGES 

·  Application air quality


 DOWNLOADS 

560 Continuous SO2 Ambient Monitor21
(PDF, 591KB)