All Categories > By Primary Gas to be Measured > Carbon Dioxide Analyzers (CO2) > Wall-mounted Ambient Air Monitors (CO2) > Continuous Carbon Dioxide Alarm Monitors - 523 Series > Item # Model 523P  
Download PDF Download PDF     Printable Page     Email Email This Page     Save To Favorites Save To Favorites

Item # Model 523P, Continuous Carbon Dioxide (CO2) Alarm Monitor, diffusion sensor



For continuous carbon dioxide (CO2) monitoring of controlled atmosphere (C/A) food storage rooms, breweries, wineries, food packaging plants, or any area where CO2 is handled.

The Nova 523 Series Carbon Dioxide alarm monitors are designed for the continuous detection of CO2 in ambient air or in air drawn from a confined space or C/A room. A built-in sample pump draws in a sample through a filter and flowmeter and then on to the CO2 detector. This model uses a solid state infrared CO2 detector which continuously detects and displays the CO2 on a front panel digital meter. A 0-1V or 4-20mA linear output signal is available for input to a recorder or similar device.

Model 523P has a built-in pump sensor.


Image




Specifications  · Applications  · Features  · Options  · Calibration  · Unique Applications

Specifications

Method of Detection

PPM CO2 by infrared detector

Ranges Available

0-5,000 PPM standard

Resolution

10 PPM

Accuracy & Repeatability

±2% of full scale

Drift

Less than 2% of full scale per week, whichever is greater

Response Time (T-90)

Less than 15 seconds to 90% step change

Ambient Temperature Range

32 to 120°F (0 to 40°C), may be operated at lower temperature with auxiliary heater

Linearity

±2% of full scale

Size & Weight

14" H x 12" W x 8" D (35.6 x 30.5 x 20.3 cm) @ 18 lbs. (8.2 kg)

Power

115 VAC, 60 Hz
220 VAC, 50 Hz

Output Options

0-1 VDC
4-20 mA


Applications
    For continuous carbon dioxide (CO2) monitoring of controlled atmosphere (C/A) food storage rooms, breweries, wineries, food packaging plants, or any area where CO2 is handled.




Features
  • Standard infrared detector
  • Fast warm-up, approx. 1 minute
  • Bright digital readout - no reading interpretation errors.
  • Easy use and calibrate
  • Easy to maintain modular layout
  • 4-20mA output signal for recording
  • NEMA 12 fiberglass enclosure is standard




Options
  • 'Fail Safe' alarms available
  • Strobe light
  • NEMA 4 or 4X enclosures
  • Cold weather package for operation to -5°F (-20°C)




Calibration

  • Ambient air for O2 and to zero all other gases
  • Analyzed calibration gas with representative concentrations for span of all other gases



Unique Applications
    All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova. In many cases, we are able to build an analyzer specific to your needs.



 DOWNLOADS 

523 Continuous CO2 Monitor
(PDF, 842KB)