Print Back
Designed to monitor Carbon Monoxide (CO) in underground parking garages, service garages, around steel making furnaces, breathing air, or any other ambient area where CO may be present.
500flexismallcabN42
Unit of Measure
Items 500flexismallcabN42
Model 580D/P
Model 580 D or P, Ambient Carbon Monoxide Monitor, diffusion or pump, Wall Mounted
500DR1
Model 580DR
Model 580DR, Carbon Monoxide Alarm Monitor, with remote sensor(s), Wall Mounted
500flexismallcabN42
Model 580BA
Model 580BA, Carbon Monoxide Alarm Monitor, Breathing Air Monitor for Compressed Air Lines with Pressure Regulator and a Special 0-50 PPM Low Range CO Sensor
Method of Detection N/A Electrochemical CO sensor
Ranges Available N/A 0-200 PPM standard on all models, except 580BA which has a 0-50 PPM sensor N/A 0-200 PPM standard on all models, except 580BA which has a 0-50 PPM sensor N/A 0-50ppm CO (lower than standard range for supplied breathing air applications)
Accuracy & Repeatability N/A Better than 1% of full scale
Drift N/A Less than 1% of full scale per week
Response Time (T-90) N/A Less than 15 seconds to 90% step change
Ambient Temperature Range N/A 40° to 104°F (5° to 40°C)
Linearity N/A ± 1% of full scale
Size & Weight N/A 20" H x 16" W x 10" D @ 20lbs. (51 x 41 x 26 cm @ 10kg)
Output Options N/A 4-20 mA N/A 4-20mA non-isolated N/A 4-20 mA
Alarms N/A Audible alarm with 'Acknowledge' button Dual high CO alarm light and relays (SPDT - 5A@ 230 VAC) Strobe light and/or large audible alarm horn available N/A Audible alarm with 'Acknowledge' button Dual high CO alarm light and relays (SPDT - 5A@ 230 VAC) Strobe light and/or large audible alarm horn available N/A Dual high CO alarm light and relays (SPDT - 5A@ 230 VAC) Low flow alarm available on Models 580BA Strobe light and/or large audible alarm horn available
Options N/A Low flow alarm on pumped sample models Strobe light N/A Low flow alarm on pumped sample models Strobe light N/A Strobe light
Analyzer Type N/A Ambient CO analyzer
Area Rating N/A General Purpose Non-Hazardous only