Optional dual level alarm with local indication, relay contacts, and audible alert available. Alarm set points are pre-set at Nova but are field adjustable if desired. Flashing strobe light and upgraded cabinets also available.
Models:
- 580D - Diffusion sensor, no pump and no moving parts; excellent for CO monitoring in immediate local environment
- 580P - Pumped sample version; pump pulls air sample from wider area or from another isolated environment, such as from a closed room
Specifications
Method of Detection |
N/A Electrochemical CO sensor |
Ranges Available |
N/A 0-200 PPM standard on all models, except 580BA which has a 0-50 PPM sensor |
Resolution |
N/A 1 PPM CO |
Accuracy & Repeatability |
N/A Better than 1% of full scale |
Drift |
N/A Less than 1% of full scale per week |
Response Time (T-90) |
N/A Less than 15 seconds to 90% step change |
Ambient Temperature Range |
N/A 40° to 104°F (5° to 40°C) |
Linearity |
N/A ± 1% of full scale |
Size & Weight |
N/A 20" H x 16" W x 10" D @ 20lbs. (51 x 41 x 26 cm @ 10kg) |
Power |
N/A 115 VAC, 60 Hz 220 VAC, 50 Hz |
Output Options |
N/A 4-20 mA |
Alarms |
N/A Audible alarm with 'Acknowledge' button Dual high CO alarm light and relays (SPDT - 5A@ 230 VAC) Strobe light and/or large audible alarm horn available |
Analyzer Type |
N/A Ambient CO analyzer |
Area Rating |
N/A General Purpose Non-Hazardous only |
Applications
N/A Designed to monitor carbon monoxide (CO) in underground parking garages, service garages, around steel making furnaces, breathing air, or any other area where CO may be present. |
Features
N/A
|
Options
N/A
|
Unique Applications
N/A The 580 Series is not suitable for process or flue gas CO analysis. All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova at 1-800-295-3771. In many cases, we are able to build an analyzer specific to your needs. |