Print Back
The Nova 580 Series carbon monoxide (CO) alarm monitors are designed for the continuous detection of CO in air. The CO sensor is of the disposable electrochemical type with an expected life of between 3-4 years. The sensor needs no warm up time and is ready to go as soon as the monitor is turned on.

Optional dual level alarm with local indication, relay contacts, and audible alert available. Alarm set points are pre-set at Nova but are field adjustable if desired. Flashing strobe light and upgraded cabinets also available.




Models:
  • 580BA - Supplied Breathing Air Monitor for compressed air lines with pressure regulator and a special 0-50 PPM low range CO sensor
Unit of Measure

Specifications

Method of Detection

N/A Electrochemical CO sensor

Ranges Available

N/A 0-50ppm CO (lower than standard range for supplied breathing air applications)

Resolution

N/A 1 PPM CO

Accuracy & Repeatability

N/A Better than 1% of full scale

Drift

N/A Less than 1% of full scale per week

Response Time (T-90)

N/A Less than 15 seconds to 90% step change

Ambient Temperature Range

N/A 40° to 104°F (5° to 40°C)

Linearity

N/A ± 1% of full scale

Size & Weight

N/A 20" H x 16" W x 10" D @ 20lbs. (51 x 41 x 26 cm @ 10kg)

Power

N/A 115 VAC, 60 Hz 220 VAC, 50 Hz

Output Options

N/A 4-20 mA

Alarms

N/A Dual high CO alarm light and relays (SPDT - 5A@ 230 VAC) Low flow alarm available on Models 580BA Strobe light and/or large audible alarm horn available

Analyzer Type

N/A Ambient CO analyzer

Area Rating

N/A General Purpose Non-Hazardous only

Applications

N/A Designed to monitor carbon monoxide (CO) in underground parking garages, service garages, around steel making furnaces, breathing air, or any other area where CO may be present.

Features

N/A

  • Fast response to the presence of CO
  • Instant warm up, no wait
  • Bright digital readout
  • Easy use and calibrate
  • Modular layout that is easy to maintain
  • 4-20mA output non-isolated
  • NEMA 12 dust-tight enclosure

Options

N/A

  • Low range version for breathing air supplies
  • CO alarm with relay contact and 'Sonalert'
  • Audible alarm with 'Acknowledge' button
  • Low flow alarm
  • NEMA 4 weather-proof enclosure
  • Bright red strobe light for visible alarming

Unique Applications

N/A The 580 Series is not suitable for process or flue gas CO analysis. All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova at 1-800-295-3771. In many cases, we are able to build an analyzer specific to your needs.