Print Back

Designed to monitor ambient hydrogen sulfide (H2S) near industrial processes such as biogas & syngas production, landfills, in confined spaces, or any other area where H2S may be present.

Unit of Measure

Specifications

Method of Detection

N/A Disposable electrochemical cell

Ranges Available

N/A 0-20 PPM standard

Resolution

N/A 1 PPM

Accuracy & Repeatability

N/A ±1% of full scale or 2 PPM, which ever is higher

Drift

N/A Less than 1% of full scale or 2 PPM per week, whichever is greater

Response Time (T-90)

N/A Less than 15 seconds to 90% step change

Ambient Temperature Range

N/A 32 to 120°F (0 to 40°C), may be operated at lower temperature with auxiliary heater

Linearity

N/A ±1% of full scale or 1 PPM, which ever is higher

Size & Weight

N/A 14" H x 12" W x 8" D (35.6 x 30.5 x 20.3 cm) @ 18 lbs. (8.2 kg)

Power

N/A 115 VAC, 60 Hz 220 VAC, 50 Hz

Output Options

N/A 0-1 VDC 4-20 mA

Applications

N/A

    Designed for the continuous, including remote, monitoring of hydrogen sulfide(H2S) in ambient air.

Features

N/A

  • Standard electrochemical cell
  • Instant warm-up, no wait
  • Bright digital readout - no reading interpretation errors.
  • Easy use and calibrate
  • Easy to maintain modular layout
  • 4-20mA output signal for recording
  • NEMA 12 fiberglass enclosure is standard

Options

N/A

  • 'Fail Safe' alarms available
  • Strobe light
  • NEMA 4 or 4X enclosures
  • Cold weather package for operation to -5°F (-20°C)

Calibration

N/A

  • Ambient air for O2 and to zero all other gases
  • Analyzed calibration gas with representative concentrations for span of all other gases

Unique Applications

N/A

    All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova. In many cases, we are able to build an analyzer specific to your needs.