Method of Detection |
N/A Infrared detector for CO2 Long life electrochemical O2 sensor |
Ranges Available |
N/A 0-20% CO2 (other ranges available) 0-25% O2 |
Resolution |
N/A 0.1% O2 and CO2 |
Accuracy & Repeatability |
N/A Within ±2% full scale |
Drift |
N/A Within 1% full scale per 8 hours of continuous operation |
Response Time (T-90) |
N/A O2 less than 10 seconds; CO2 less than 30-40 seconds to T-90 |
Ambient Temperature Range |
N/A 4 to 49 ºC40 to 120 ºF |
Linearity |
N/A ±1.0% of full scale |
Size & Weight |
N/A approx. 26 x 18 x 13 cm @ 3.4 kg (10" x 7" x 5" @ 7.5lbs) |
Power |
N/A 115 VAC / 60 Hz for recharging (220VAC / 50Hz also available.) |
Output Options |
N/A 4-20mA |
Hazardous Area Rating Options |
N/A General Purpose, Non-Hazardous |
N/A Analysis of Carbon Dioxide (CO2) and Oxygen (O2). For checking combustion efficiency, burner & control performance of furnaces, heaters and boilers in commercial, industrial and residential applications. |
N/A
|