The Nova 380 Series Tri-Gas Analyzer is designed for monitoring H2 purity inside a power generator and to monitor the purging procedure during a generator shut down or start up.
The analyzer contains a temperature compensated thermal conductivity (T/C) cell, amplifier board, digital readout, range switch, pressure regulator, gas flow control valve, pump and a flow indictor. A 4-20mA recorder output follows the active reading.
The T/C cell does not burn the sample nor is it consumed in any way, so it has a life expectancy of over 10 years. Measurement results are fast and accurate. A rechargeable battery provides power for about 8 hours of operation, and the analyzer can be used while it is being recharged.
Method of Detection |
N/A Temperature compensated thermal conductivity (T/C) cell |
Ranges Available |
N/A Range 1 : 0-100% H2 in Air Range 2 : 0-100% H2 in CO2 Range 3 : 0-100% Air in CO2 |
Resolution |
N/A 0.1% of gas measured |
Accuracy & Repeatability |
N/A Range 1: ± 1% of Full Scale; Range 2: ± 2% of F.S.; Range 3: ± 2% of F.S. |
Drift |
N/A H2 in Air range is ± 0.4% per week H2 in CO2 or Air in CO2 2% F.S. per week maximum drift |
Response Time (T-90) |
N/A 10-15 seconds to 90% step change - not including sample transport time |
Ambient Temperature Range |
N/A 0 to 50 ºC32 to 120 ºF |
Linearity |
N/A ±1.0% of F.S. on H2 in Air range. ±2% of F.S. in H2 or Air in CO2 ranges |
Size & Weight |
N/A 9 1/2" L x 7" W x 6 1/2" H @ 12 lbs (24 x 17 x 18 cm @ 3.6 kg) |
Power |
N/A Battery operation. 115 VAC, 60 Hz for recharging (220 VAC, 50 Hz available) |
Output Options |
N/A 4-20mA |
Hazardous Area Rating Options |
N/A General Purpose, Non-Hazardous |
N/A
|
N/A
|