The monitors all utilize a long life electrochemical O2 sensor. Actual O2 concentration is shown on a digital meter. Alarm set points are pre-set at Nova but are field adjustable if desired. A 'Sonalert' audible alarm with reset button is included.
Specifications
Method of Detection |
N/A Customer replaceable electrochemical 'fuel cell' oxygen sensor, expected life 5 years |
Ranges Available |
N/A 0-30% O2 |
Resolution |
N/A 0.1% O2 |
Accuracy & Repeatability |
N/A ±2% of full scale |
Drift |
N/A Less than 1% of full scale per month |
Response Time (T-90) |
N/A 6-8 seconds to 90% step change |
Ambient Temperature Range |
N/A 32 to 122°F (0 to 50°C), may be operated at lower temperature with auxiliary heater |
Linearity |
N/A ±2% of full scale |
Size & Weight |
N/A 10" H x 8" W x 6" D (25.4 x 20.3 x 15.2 cm) @ 6 lbs. (2.7 kg) |
Power |
N/A 115 VAC, 60 Hz 220 VAC, 50 Hz |
Output Options |
N/A 0-1 VDC 4-20 mA |
Alarms |
N/A Optional: High and low SPDT contacts with 10 A, 115 VAC rating; Two alarm levels; 'Sonalert' audible alarm with reset button; Indicator light for each alarm level; Strobe light and 'fail safe' alarms available |
Analyzer Type |
N/A O2 Gas Analyzer |
Applications
N/A
|
Features
N/A
|
Options
N/A
|
Product Catalog
Contact Us
Request Quote