New Call-to-action
The Nova 310 Series Portable Flue Gas CO Analyzer utilizes a reliable, customer-replaceable electrochemical sensor which responds quickly to the CO present in the flue gas sample. Its life expectancy is between 3 and 4 years.

In operation, a built-in sample pump draws in the flue gas sample through the probe, sample house, condensate removal filter, secondary filter, flow meter, and then on to the CO detector. The detected CO is displayed on a digital meter.

A rechargeable battery powers the pump and electronics. The analyzer can still be operated while it is being charged. The analyzer is supplied with approximately 12 ft. (4 m) of sample hose and a short stainless steel tube probe.

Specifications

Method of Detection

N/A Customer replaceable electrochemical CO sensor

Ranges Available

N/A 0-200 up to 0-9999 PPM CO

Resolution

N/A 1 PPM in PPM range

Accuracy & Repeatability

N/A Better than 1% of full scale, based on a 0-2000 PPM range

Drift

N/A Less than 1% full scale per month

Response Time (T-90)

N/A 20-30 seconds

Ambient Temperature Range

N/A 0 to 50 ºC32 to 122 ºF

Linearity

N/A Better than 1.0% of full scale

Size & Weight

N/A approx. 26 x 18 x 13 cm @ 3.4 kg (10" x 7" x 5" @ 7.5lbs)

Power

N/A 115 VAC / 60 Hz for recharging (220 VAC / 50 Hz available)

Output Options

N/A 4-20mA

Analyzer Type

N/A CO analyzer

Hazardous Area Rating Options

N/A General Purpose, Non-Hazardous

Applications

N/A

    For boiler or furnace flue gas analysis where a continuous oxygen analyzer already exists, but carbon monixode (CO) must still be measured.

Features

N/A

  • Rugged design that is easy to operate and maintain
  • Fast warm-up and response
  • Disposable, long life electrochemical CO sensor
  • Rechargeable battery operation
  • Use on flue gas from any fuel
  • Choice of ranges: 0-200 up to 0-9999 PPM CO
  • Built in sample pump, filter and flowmeter
  • Condensate removal
  • Rapid reading recovery after CO 'overdose'
  • Stainless steel probe with sample hose

Options

N/A

  • Recorder output - 4-20mA
  • Stack temperature readout
  • Special sampling probes
  • Sample pre-cooler
  • Suitcase (K) style cabinet
  • On-board data logging to USB stick

Calibration

N/A

  • Air for zero
  • Analyzed calibration gas mixture of PPM CO in nitrogen for span.

Unique Applications

N/A

    All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova. In many cases, we are able to build an analyzer specific to your needs.