All Categories > Multigas Analyzers > Item # 313 Series  
Download PDF Download PDF     Printable Page     Email Email This Page     Save To Favorites Save To Favorites

Item # 313 Series, Portable Flue Gas Analyzer for Oxides of Nitrogen



The Nova 313 Series Portable Flue Gas Analyzer for NO, NO2, or NOx utilizes reliable, stable NO and/or NO2 sensors which respond quickly to the NO or NO2 present in flue gases or engine exhaust. NO is the major component (90-95%) of the NOx found in flue gases or engine exhaust (except diesel).

In operation, a built in sample pump draws in the gas sample through the S.S. probe, 12 ft sample hose, condensate removal filter, secondary filter and flowmeter, then on to both sensors. The output of each sensor is then amplified and displayed on a large LCD digital meter with backlight. A selector switch allows the two gases to be read individually or as a total (NOx).

The rechargeable battery provides enough power for about 20 hours of continuous operation and the analyzer can be used while it is being recharged. A red LED tells when to recharge and a green LED verifies that it is receiving recharging power. The recharger plus a stainless steel probe with 12 ft. (4 m) hose are included.






 Specifications   Applications   Features   Options   Calibration   

Method of Detection

Customer replaceable electrochemical nitric oxide and nitrogen dioxide sensors Expected life 2-3 year each

Ranges Available

0-2000 PPM NO; 0-800 PPM NO2; 0-2000 PPM Nox; (0-5000 PPM available) Ranges switch selectable

Resolution

1 PPM on 0-2000 PPM; 10 PPM on higher ranges

Accuracy & Repeatability

Better than 2% full scale

Drift

Within 1% of full scale per 8 hours of continuous operation

Response Time (T-90)

20-30 seconds

Ambient Temperature Range

12 to 49 ºC
55 to 120
ºF

Linearity

±2% of full scale

Size & Weight

10" L x 7 1/2" H x 8" D @ 8 lbs (25 x 19 x 20 cm @ 3.6 kg)

Power

AC/DC Operation, 115 VAC, 60 Hz for recharging (Other voltages available)

Output Options

4-20 mA or 0-1 VDC

Alarms

NO, NO2 or NOx alarms with LED

Unique Applications

    All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova. In many cases, we are able to build an analyzer specific to your needs.

Primary Gas to be Measured

Oxides of Nitrogen (NOx)

Industry Type

Flue Gas or Emissions


 MORE IMAGES 

·  Application flue gas

·  Precooler


 DOWNLOADS 

313 Portable NOx Flue Analyzer
(PDF, 658KB)