New Call-to-action
Analysis of Carbon Monoxide (CO), Carbon Dioxide (CO2), Sulfur Dioxide (SO2), and Oxide of Nitrogen (NOx) emissions. For checking combustion efficiency, burner & control performance, and detection of air infiltration on furnaces, heaters and boilers. May be used in commercial, industrial and residential settings.
Unit of Measure
Items
5000 Portable Flue Gas Analyzer

Portable Flue Gas Analyzer for O2 and CO

5000 Portable Flue Gas Analyzer

Portable Flue Gas Analyzer for CO and NOx

5000 Portable Flue Gas Analyzer

Portable Flue Gas Analyzer for O2, CO2, and CO

5000 Portable Flue Gas Analyzer

Portable Flue Gas Analyzer for O2, CO2, CO, and NOx

Portable Flue Gas Analyzer for O<sub>2</sub>, CO<sub>2</sub>, CO, NOx, and SO<sub>2</sub>

Portable Flue Gas Analyzer for O2, CO2, CO, NOx, and SO2
Method of Detection N/A Customer replaceable electrochemical O2, CO, SO2, and NO sensors Solid state infrared detector for CO2
Ranges Available N/A 0-1800°F (0-1000 °C) net stack temperature 0-20.00% CO2 0-200 or 0-2000 PPM NOx (as NO or NO + NO2) 0-200 or 0-2000 PPM SO2 0-25.0 % O2 0-9999 PPM CO
Resolution N/A ±0.1% CO2, 1 PPM, 1°F (1°C)
Accuracy & Repeatability N/A ±10 PPM for all gases 0.1%
Drift N/A <2% full scale per 8 hours of continuous operation
Response Time (T-90) N/A < 30 seconds for 90% of O2, CO2, CO and SO2, < 60 seconds for 90% NO
Ambient Temperature Range N/A Operating : 32 to 122°F (0 to 50°C); Sample : Up to 1200°F (635°C) (standard probe)
Linearity N/A ±1% of full scale for each gas measured
Power N/A 12 V battery operation, 115 VAC, 60 Hz for recharging 220 VAC, 50 Hz
Output Options N/A 0-1 V for each gas measured. RS232 or RS485, printer 4-20 mA
Applications N/A
    Analysis of carbon Monoxide (CO), carbon dioxide (CO2), sulfur dioxide (SO2), and oxide of nitrogen (NOx) emissions. For checking combustion efficiency, burner & control performance, and detection of air infiltration on furnaces, heaters and boilers. May be used in commercial, industrial and residential settings.
Features N/A
  • Rugged design that is easy to use
  • Fast warm-up and accurate response
  • Modular layout that is easy to maintain
  • Digital readouts with switchable backlight
  • Built in sample pump
  • Rechargeable battery operation
  • Active condensate removal
  • Thermocouple temperature probe
  • Long-life electrochemical sensors for O2, CO, SO2, and NOx
  • Wide CO2 measurement range actually measured by infrared detector - not calculated
  • NOx can be NO only or combined NO and NO2
  • Rapid reading recovery on CO, NOx, or SO2 'overdose'
  • Use on any fuel
  • Pays for itself in months through fuel savings
Options N/A
  • Sample pre-cooler
  • RS-232 or RS-485 output
  • Built in printer
  • Stack temperature readout
  • NOx as NO and NO2
  • High temperature sampling probe
  • Data logger for PC computer
Options N/A Built in printer Data logger for PC computer High temperature sampling probe NOx as NO and NO2 RS-232 or RS-485 output Sample pre-cooler Stack temperature readout
Calibration N/A
  • Ambient air for O2 span, CO2 zero, CO zero, SO2 zero, and NOx zero
  • On analyzed gas mixtures of CO2 and CO in nitrogen, NO in nitrogen, and SO2 in nitrogen for span (also zeroes O2)
Analyzer Type N/A Flue Gas Analyzer
THIRD GAS to be Measured N/A Carbon Monoxide (CO) Oxygen (O2) N/A Carbon Monoxide (CO) Oxides of Nitrogen (NOx) N/A Carbon Dioxide (CO2) Carbon Monoxide (CO) Oxygen (O2) N/A Carbon Dioxide (CO2) Carbon Monoxide (CO) Oxides of Nitrogen (NOx) Oxygen (O2) N/A Carbon Dioxide (CO2) Carbon Monoxide (CO) Oxides of Nitrogen (NOx) Oxygen (O2) Sulfur Dioxide (SO2)
View Our
Product Catalog
Have a question?
Contact Us
Ready to get started?
Request Quote