New Call-to-action
Analysis of Oxygen (O2), Carbon Monoxide (CO), Carbon Dioxide (CO2) and Oxides of Nitrogen (NOx as NO). For checking the combustion efficiency and burner & control performance of furnaces, heaters, and boilers. May be used in commercial, industrial, and residential settings.
Unit of Measure
Items
376-WP-O2--CO--CI2--NOx

Portable Flue Gas Analyzer for Oxygen, Carbon Monoxide, Carbon Dioxide and Oxides of Nitrogen, Weatherproof (WP) Enclosure

K-4-gas

Portable Flue Gas Analyzer for Oxygen, Carbon Monoxide, Carbon Dioxide and Oxides of Nitrogen, Suitcase (K) Enclosure
Method of Detection N/A Customer replaceable electrochemical O2, CO and NO sensors Solid state infra-red detector for CO2 N/A Customer replaceable electrochemical O2, CO and NO sensors Solid state infrared detector for CO2
Ranges Available N/A 0-20.0% CO2 0-200 to 0-2000 PPM NOx (as NO) ranges available 0-2000 PPM and 0-4.00% CO - Switch selectable 0-25.0% O2 N/A 0-1800°F (0-1000°C) stack temperature 0-20.0% CO2 0-200 to 0-2000 PPM NOx (as NO) ranges available 0-2000 PPM and 0-4.00% CO - Switch selectable 0-25.0% O2
Resolution N/A 0.1% O2 and CO2, 1 PPM CO and NOx N/A
Accuracy & Repeatability N/A Within ±0.1% O2 and CO2; ±10 PPM CO and NO
Drift N/A 2% full scale per 8 hours of continuous operation
Response Time (T-90) N/A 10-15 seconds for O2; 20-30 seconds for CO, NO, and CO2
Ambient Temperature Range N/A 0 to 40 ºC32 to 105 ºF
Linearity N/A ±1.0% of full scale for each gas measured
Size & Weight N/A 16" L x 4 1/2" H x 8" D @ 13 lbs (40.6 x 20.3 x 10.8 cm @ 5.6 kg) N/A 18" L x 7" H x 12" D @ 15 lbs (45.7 x 30.5 x 17.8 cm @ 6.8 kg)
Power N/A AC/DC Operation, 115 VAC 60 Hz for recharging (Other voltages available.) N/A AC/DC Operation, 115 VAC, 60 Hz for recharging
Output Options N/A 4-20 mA or 0-1 VDC N/A 0-1 VDC 4-20 mA
Options N/A AC power only operation Detachable/portable Data Logger Gas alarms with LED Outputs of 0-1 V or 4-20 mA (can be isolated) Special sampling probes Suitcase (K) style cabinet available N/A AC power only operation Detachable/portable Data Logger Gas alarms with LED Outputs of 0-1 V or 4-20 mA (can be isolated) Special sampling probes Stack temperature readout (376T) Suitcase (K) style cabinet available
Analyzer Type N/A Multigas Flue Gas Analyzer
Hazardous Area Rating Options N/A General Purpose, Non-Hazardous
View Our