Item # Model 550D, Hydrogen Sulfide Alarm Monitor, diffusion sensor
Designed to monitor ambient hydrogen sulfide (H2S) near industrial processes such as biogas & syngas production, landfills, in confined spaces, or any other area where H2S may be present.
Less than 1% of full scale or 2 PPM per week, whichever is greater
Response Time (T-90)
Less than 15 seconds to 90% step change
Ambient Temperature Range
32 to 120°F (0 to 40°C), may be operated at lower temperature with auxiliary heater
Linearity
±1% of full scale or 1 PPM, which ever is higher
Size & Weight
14" H x 12" W x 8" D (35.6 x 30.5 x 20.3 cm) @ 18 lbs. (8.2 kg)
Power
115 VAC, 60 Hz 220 VAC, 50 Hz
Output Options
0-1 VDC 4-20 mA
Applications
Designed for the continuous, including remote, monitoring of hydrogen sulfide(H2S) in ambient air.
Features
Standard electrochemical cell
Instant warm-up, no wait
Bright digital readout - no reading interpretation errors.
Easy use and calibrate
Easy to maintain modular layout
4-20mA output signal for recording
NEMA 12 fiberglass enclosure is standard
Options
'Fail Safe' alarms available
Strobe light
NEMA 4 or 4X enclosures
Cold weather package for operation to -5°F (-20°C)
Calibration
Ambient air for O2 and to zero all other gases
Analyzed calibration gas with representative concentrations for span of all other gases
Unique Applications
All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova. In many cases, we are able to build an analyzer specific to your needs.