Canada
270 Sherman Avenue N. Hamilton, ON L8L 6N5
Phone: (905) 545 2003• Fax: (905) 545 4248 |
United States
1925 Pine Avenue Niagara Falls, NY 14301
Phone: (716) 285-0418 • Fax: (716) 282-2937 |
|
Email: sales@nova-gas.com or websales@nova-gas.com
|
|
|
|
|
Item # Model 436RMN7, Model 436RMN7, Tri-Gas Analyzer for Hydrogen Cooled Power Generators, Gas Detector in Explosion-proof Cabinet; Control Section in General Purpose Rack Mount Cabinet
|
|
|
|
The Nova 436 Series Tri-gas analyzer is designed specifically for monitoring H2 purity in a power generator and to monitor the purging procedure during shut down. The analyzer can measure the following gases by switch selection:
Range 1: 0-100.0% H2 in Air Range 2: 0-100.0% H2 in CO2 Range 3: 0-100.0% Air in CO2
A 4-20mA recorder output is provided for the range of 85-100% H2 in Air. The Model 436 analyzer is typically available in a single ex-proof cabinet with all capabilties built-in. Or, it may be divided into 2 sections that are electrically connected. The control section contains the main microprocessor boards as well as the touch-screen display, alarm contacts, and calibration & function switches. The gas detector section contains the temperature-controlled thermal-conductivity (TC) cell, solenoid valves, gas pressure regulator, flow meter, and 2 flame arrestors. Either the gas detector section on its own or both gas detector and control sections may be purchased in explosion-proof cabinets. The explosion-proof cabinets are UL listed and CSA certified for use in Class 1, Division 1, Groups BCD hazardous areas. If the gas detector section only is explosion-proof, the control section is typically enclosed in a 19" rack mount cabinet for use in a general purpose, non-hazardous area. The control section can also be mounted in a NEMA 4 wall mount cabinet.
Cabinets, 436RMN7: gas detector in Class 1, Division 1, Groups BCD explosion proof cabinet; control section in general purpose 19" rack mount cabinet
|
|
|
|
|
|
|
For continuous analysis of hydrogen (H2) purity and for purge monitoring of hydrogen-cooled generators and synchronous converters.
|
|
|
|
- One analyzer monitors all 3 gases for purity (Range 1) or purging (Ranges 2 and 3):
- Range 1: 0-100% H2 in Air
- Range 2: 0-100% H2 in CO2
- Range 3: 0-100% Air in CO2
- Bright digital readout
- 4-20mA isolated output for 85-100% of H2 in Air
- Thermal-conductivity cell with high accuracy and repeatability, cannot be burned out
- Explosion-proof gas detector enclosure suitable for Class 1 Division 1 Group BCD rated areas
- Fast response (T90 -10 to 15sec)
- Fast 'one-touch' automated calibration
- Built-in pressure regulator and line pressure indication
- 2 levels of low H2 purity alarms
|
|
|
|
- Hi/Low gas and low flow alarms available
- Isolated analog, RS485 outputs available
|
|
|
|
- Channel 1 - Air for Zero, 100% H2 for Span
- Channel 2 - 100% CO2 for Zero, 100% H2 for Span
- Channel 3 - 100% CO2 for Zero, Air for Span
|
|
|
|
|
|
|
|
|
|
|
|
|
|