All Categories > Multigas Analyzers > Item # 436 Series  


Item # 436 Series, Tri-Gas Analyzer to Monitor Purity and Purging of Hydrogen Cooled Power Generator


The Nova Model 436 Series Tri-gas analyzer is designed specifically for monitoring H2 purity in the H2 feed to a power generator and to monitor the purging procedure during shut down. The analyzer can measure the following gases by switch selection :
Range 1: 0-100.0% H2 in Air
Range 2 : 0-100.0% H2 in CO2
Range 3 : 0-100.0% Air in CO2
A 4-20 mA output is provided for the range of 85-100% H2 in air, along with two gas alarms and a sensor fail alarm.





 Specifications 

Method of Detection

Temperature controlled thermal conductivity (T/C) cell, cannot be burned out due to loss of flow or changing gases

Ranges Available

Range 1 : 0-100% H2 in Air
Range 2 : 0-100% H2 in CO2

Range 3 : 0-100% Air in CO2

Resolution

±0.1% of gas measured

Accuracy & Repeatability

±1% F.S except in 85-100% H2 in Air range which is within 0.2% absolute H2

Drift

H2 in CO2 or Air in CO2 1% F.S. per week maximum drift, 0-100% H2 in Air range is ±0.2% per week

Response Time (T-90)

10-15 seconds to 90% step change - not including sample transport time

Ambient Temperature Range

0 to 49 ºC
32 to 122
ºF

Linearity

±0.4% of F.S. on H2 in Air range, ±1% of F.S. in H2 or Air in CO2 ranges

Size & Weight

Dimensions will vary depending on enclosure style and options required

Power

115 VAC, 60 Hz
220 VAC, 50 Hz

Output Options

4-20 mA into 500 ohms non-isolated standard
Isolated 4-20 mA, RS232, RS485, MODBUS, Ethernet outputs

Alarms

Alarm set points are field adjustable
Alarms have front panel light for each alarm and SPST (normally energized) relay with 5A rating at 250VAC non-inductive load

Dual alarms are provided for low H2 purity. Detector fail alarm also provided as standard

Primary Gas to be Measured

Carbon Dioxide (CO2)
Hydrogen (H2)

Industry Type

Power Industry

Mounting Options

Panel Mount
Rack Mount

Models and Enclosure Options

NEMA 4



Print Back