Canada
270 Sherman Avenue N.
Hamilton, ON L8L 6N5
Phone: (905) 545 2003• Fax: (905) 545 4248
United States
1925 Pine Avenue
Niagara Falls, NY 14301
Phone: (716) 285-0418 • Fax: (716) 282-2937
 
Email: sales@nova-gas.com or websales@nova-gas.com
All Categories > Multigas Analyzers > Item # 380 Series  


Item # 380 Series, Portable Tri Gas Analyzer for Hydrogen Purging


The Nova 380 Series Tri-Gas Analyzer is designed for monitoring H2 purity inside a power generator and to monitor the purging procedure during a generator shut down or start up.

The analyzer contains a temperature compensated thermal conductivity (T/C) cell, amplifier board, digital readout, range switch, pressure regulator, gas flow control valve, pump and a flow indictor. A recorder output is optional.

The T/C cell does not burn the sample nor is it consumed in any way, so it has a life expectancy of over 10 years. Measurement results are fast and accurate. A rechargeable 'gel cell' battery provides enough power for about 8 hours of continuous operation and the analyzer can be used while it is being recharged.





 Specifications 

Method of Detection

Temperature compensated thermal conductivity (T/C) cell

Ranges Available

Range 1 : 0-100% H2 in Air
Range 2 : 0-100% H2 in CO2

Range 3 : 0-100% Air in CO2

Resolution

0.1% of gas measured

Accuracy & Repeatability

±1% F.S except in 85-100% H2 in Air range, which is within 0.5% absolute H2

Drift

0-100% H2 in Air range is ± 0.4% per week
H2 in CO2 or Air in CO2 2% F.S. per week maximum drift

Response Time (T-90)

10-15 seconds to 90% step change - not including sample transport time

Ambient Temperature Range

0 to 50 ºC
32 to 120
ºF

Linearity

±1.0% of F.S. on H2 in Air range. ±2% of F.S. in H2 or Air in CO2 ranges

Size & Weight

K Style: 9 1/2" L x 7" W x 6 1/2" H @ 12 lbs (24 x 17 x 18 cm @ 3.6 kg)
WP Style: 11 1/2" L x 8" W x 7 1/4" H @ 8 lbs (29 x 20 x 18 cm @ 3.6 kg)

Power

AC/DC Operation. 115 VAC, 60 Hz for recharging (220 VAC, 50 Hz available)

Output Options

4-20 mA or 0-1 VDC

Unique Applications

All Nova analyzers are built using proven technologies and techniques. If this product does not suit your application, please contact Nova. In many cases, we are able to build an analyzer specific to your needs.

Primary Gas to be Measured

Hydrogen (H2)

Industry Type

Power Industry



Print Back